Circuit breaker is composed as one of electrical
power system. As an expensive switch gear, it not
only breaks a load current but also a fault current,
serving as a practical implementing role in system
management, control, and protection. |
|
Thus credibility of circuit breaker activation is
directly related to a credibility of other systems
connected with. Due to this, effort to prevent circuit
breaker and protection system fault should be
improved. |
|
Recently, credibility of circuit breaker activation has
been improved by development of GIS (Gas
Insulation Switchgear). As diagnosis and protection
of circuit breaker continuously evolved, at present,
various types of verified systems have been
applied. |
|
Protection relay for 345 [kV] circuit breaker failure
protections uses both over current protection
function for diagnosis of circuit breaker condition
and circuit breaker failure initiation function (BFI) by
circuit breaker control command. Thus it is
composed into and applied to a system in order to
prevent spread of fault, using both circuit breaker
trip commands by protection system and detection
of circuit breaker¡¯s abnormal condition. |
|
GABO¡¯s 345 [kV] circuit breaker failure protection
panel has a protection relay (7SV600) made from
SIEMENS, in order to guarantee reliability. By
having accumulated knowledge in manufacturer
technology of protection panel, and experienced
professionals, we strive to accomplish noise
immunity, stable earthing, durability, insulation,
assembly, all of which being incorporated in order
to generate products of credibility. |
 |
|
|
|
CIRCUIT BREAKER FAILURE PROTECTION SYSTEM CONFIGURATION |
|
|
Circuit Breaker failure protection system detects current flowing
through a circuit breaker and an initiating signal for circuit
breaker trip command, in order to monitor activation condition
of a circuit breaker. |
When circuit breaker failure gets detected, in order to prevent
expansion of fault, circuit breaker failure protection system trips
peripheral circuit breakers located nearby circuit breaker with
fault. |
 |
|
|
|
|
BREAKER FAILURE PROTECTION RELAY (7SV6x) SPECIFICATION |
|
|
- Digital Protection Relay with 16 Bit microprocessor |
- Independent high sensitive current detection on each phase. |
- Independent indication on each phase / 3 phase common initiation detection. |
- 2-out-of-4 current detection function |
- Single- Stage, Two- Stage time delay. |
- Remote end transfer trip. |
- Zero Sequence, negative sequence current compensation |
 |
|
|
|
|
|
CIRCUIT BREAKER FAILURE PROTECTION RELAY (7SV6x) MAIN FUNCTION |
|
- Circuit breaker failure (current/ circuit breaker condition observation) detection function. |
- Remote end transfer trip. |
- End Fault protection. |
- User defined logic (CFC-continuous function chart). |
- Function to prevent mal-function through many fault detection. |
- Self-diagnosis |
- Selection possible to one pole/three pole trip function |
- Metering (current, voltage, active/ reactive power, etc) |
- Event recording function (trip, alarm, fail, etc) |
- Using any portable computing device, setting and fault
analysis function (analysis program (DIGSI), Comrade
File conversion function) becomes possible. |
|
|
|
|
CIRCUIT BREAKER TECHNICAL SPEFICATION/STANDARD |
Index |
Item |
Specification |
Remarks |
Rating |
Power Supply |
Voltage Input |
  DC : 125[V], AC : 230[V](Frequency 50/60[hz]) |
Selectable |
Power Consumption |
  4[W] |
Analog |
Current |
  1[A], Burden : 0.1[VA]   5[A], Burden : 0.2[VA] |
  |
Digital input |
  Number of digital input : 3   Voltage Range : 24 ~ 250[VDC] |
Selectable |
Digital Output |
  Number of digital output : 4   Allowable Current : Continus(5[A]), 30[A](0.5[sec]) |
Communication |
Communication Port |
  RS-485 |
Selectable |
|
|